Characteristics
Documentation
Review
Main | |
---|---|
SKU | A9F84401 |
range of product | iC60 |
product or component type | miniature circuit-breaker |
range | Acti 9 |
device application | distribution |
device short name | iC60H |
product name | Acti 9 iC60 |
[In] rated current | 1 A |
curve code | C |
standards | EN 60898-1, EN 60947-2, IEC 60898-1, IEC 60947-2 |
number of protected poles | 4 |
network type | AC, DC |
breaking capacity code | H |
utilisation category | category A conforming to EN 60947-2, category A conforming to IEC 60947-2 |
breaking capacity | 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1, 15 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2, 70 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2, 70 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2, 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2, 70 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2, 70 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
suitability for isolation | yes conforming to EN 60898-1, yes conforming to EN 60947-2, yes conforming to IEC 60898-1, yes conforming to IEC 60947-2 |
poles description | 4P |
trip unit technology | thermal-magnetic |