SKU | LV429790 |
mounting mode | fixed |
range of product | ComPact NSX100...250 |
product or component type | circuit breaker |
range | ComPact |
device application | distribution |
device short name | NSX100H |
control type | toggle |
trip unit name | Micrologic 2.2 |
network frequency | 50/60 Hz |
utilisation category | category A |
[In] rated current | 100 A at 40 °C |
breaking capacity | 10 kA at 600 V AC 50/60 Hz conforming to UL 508, 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 65 kA at 480 V AC 50/60 Hz conforming to UL 508, 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 85 kA at 240 V AC 50/60 Hz conforming to UL 508 |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
suitability for isolation | yes conforming to EN/IEC 60947-2 |
network type | AC |
breaking capacity code | H 70 kA 415 V AC |
poles description | 3P |
protected poles description | 3t |
product name | ComPact NSX |
trip unit technology | electronic |
trip unit protection functions | LSoI |